Ref. No. | Type | Max. output power at AC operation | Family data sheet | Isolation primary - secondary | Length | Width | Height | Weight |
---|---|---|---|---|---|---|---|---|
186911 | ECXe 350.375 | 35 W | no Isolation | 280 mm | 30 mm | 16 mm | 148 g | |
186912 | ECXe 350.376 | 67 W | no Isolation | 280 mm | 30 mm | 16 mm | 151 g |
Ref. No. | Type | Max. output power at AC operation | Output current | Min. output voltage | Max. output voltage | Output ripple (100 Hz) | SVM value | Current setting / Configuration | Output current tolerance – | Output current tolerance + |
---|---|---|---|---|---|---|---|---|---|---|
186911 | ECXe 350.375 | 35 W |
50 V
50 V
50 V
50 V
|
100 V
100 V
100 V
100 V
|
3 % | < 0.4 | DIP switch | -5 % | 5 % | |
186912 | ECXe 350.376 | 67 W |
90 V
90 V
90 V
90 V
|
190 V
190 V
190 V
190 V
|
3 % | < 0.4 | DIP switch | -5 % | 5 % |
Ref. No. | Type | Max. output power at AC operation | Min. voltage | Max. voltage | Min. input voltage AC | Max. input voltage AC | Min. mains frequency | Max. mains frequency | Input current at 230 V AC with max. load | Power factor at full load (230 V) | Efficiency at full load (230 V) | THD at full load (230 V) | Standby power | No-load standby power | Inrush current | Inrush current time at 50% Ipeak | Time to light on in AC operation |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
186911 | ECXe 350.375 | 35 W | 220 V | 240 V | 198 V | 264 V | 50 Hz | 60 Hz | 173 mA | 0.95 | 0.92 | 14 % | no standby operation possible | no load operation not intended | 31 A | 101 µs | 500 ms |
186912 | ECXe 350.376 | 67 W | 220 V | 240 V | 198 V | 264 V | 50 Hz | 60 Hz | 312 mA | 0.95 | 0.945 | 12 % | no standby operation possible | no load operation not intended | 36 A | 169 µs | 500 ms |
Ref. No. | Type | Max. output power at AC operation | Min. input voltage DC | Max. input voltage DC | Input current at max. V DC with max. load | Switching time AC - DC | Switching time DC - AC | Time to light on in DC operation |
---|---|---|---|---|---|---|---|---|
186911 | ECXe 350.375 | 35 W | 198 V | 276 V | 140 mA | 200 µs | 150 µs | 600 ms |
186912 | ECXe 350.376 | 67 W | 198 V | 276 V | 254 mA | 200 µs | 150 µs | 700 ms |
Ref. No. | Type | Max. output power at AC operation | Dimmable | DALI power supply integrated | DALI power supply switchable | Min. dimming level | Max. dimming level |
---|---|---|---|---|---|---|---|
186911 | ECXe 350.375 | 35 W | No | No | 100 % | 100 % | |
186912 | ECXe 350.376 | 67 W | No | No | No | 100 % | 100 % |
Ref. No. | Type | Max. output power at AC operation | Isolation primary - secondary | Max. working voltage (Uout) | Protection against transient main peaks L–N | Protection against transient main peaks L/N–PE | Leakage current over PE |
---|---|---|---|---|---|---|---|
186911 | ECXe 350.375 | 35 W | no Isolation | 250 V | 1 kV | 2 kV | 0.3 mA |
186912 | ECXe 350.376 | 67 W | no Isolation | 300 V | 1 kV | 2 kV | 0.3 mA |
Ref. No. | Type | Max. output power at AC operation | EU Declaration of Conformity | CB certificate | ENEC certificate |
---|---|---|---|---|---|
186911 | ECXe 350.375 | 35 W | |||
186912 | ECXe 350.376 | 67 W |
Ref. No. | Type | Max. output power at AC operation | 2D data |
---|---|---|---|
186911 | ECXe 350.375 | 35 W | |
186912 | ECXe 350.376 | 67 W |
Ref. No. | Type | Max. output power at AC operation |
---|---|---|
186911 | ECXe 350.375 | 35 W |
186912 | ECXe 350.376 | 67 W |
Ref. No. | Type | ||
---|---|---|---|
186911 | ECXe 350.375 | ||
186912 | ECXe 350.376 |